Integer settings
The following table describes the Integer settings available in the ATP Settings dialog box:
Output Control
Print Freq.: Frequency of LUNIT6 output within the time-step loop. For example, a value of 3 means that every third time step will be printed. ATP parameter: IOUT
Plot Freq.: Frequency of saving solution points to the PL4 output file. For example, a value of 2 means that every second time step will be written to the PL4 file. ATP parameter: IPLOT
Plotted output: Writes ICAT=1 to the ATP file if checked. Produces a PL4 file.
MemSave: Controls the dumping of EMTP memory to disk at the end of simulation if START AGAIN request is specified. If checked indicates memory saving (START AGAIN).
Printout
Network connectivity: Writes table of connectivity written in the LUNIT6 output file if checked. ATP variable: DOUBLE.
Steady-state phasors: Writes complete steady state solution to the LUNIT6 output file if checked. Branch flows, switch flows and source injection . ATP variable: KSSOUT=1.
Extremal values: Writes extrema printed at the end of the LUNIT6 output file if checked. ATP variable: MAXOUT.
Extra printout control: Additional printout frequency control if checked. ATP variable: IPUN=-1.
Auto-detect of simulation errors
ATPDraw can be requested to automatically examine the LIS-file after a simulation and display possible problems. The user can select 5 different error/warning flags.